TAMCO Accessories
Vertical Jackshaft
connecting two vertical damper sections
Contact TAMCO Customer Service for possible configurations not shown below.
MINIMUM SIZE:
Installed in Duct:
6½”w x over 75”h (166 mm x over 1905 mm)
Flanged to Duct:
4½”w x over 75”h (115 mm x over 1905 mm)
MAXIMUM SIZE:
60”w x 120”h (1524 mm x 3048 mm) or
48”w x 150”h (1220 mm x 3810 mm)
(Limiting section width to 48” (1220 mm) allows height to increase to 75” (1905 mm) per section.)
MAXIMUM AREA:
50 ft² (4.65 m²)
Up to 50 ft² (4.65 m²):
2 motor locations. Damper to be ordered with a vertical jackshaft.
Operated with a minimum of 1 motor, direct-coupled to either the top or bottom section's drive rod.
NOTE:
Three sections cannot be connected with vertical jackhafts. A maximum of two sections can be connected vertically.
MINIMUM SIZE::
Over 60”w x over 60”h
(over 1524 mm x over 1524 mm)
MAXIMUM SIZE:
120”w x 120”h (3048 mm x 3048 mm) or
96”w x 150”h (2438 mm x 3810 mm)
(Limiting section width to 48” (1220 mm) allows height to increase to 75” (1905 mm) per section.)
MAXIMUM AREA:
100 ft² (9.29 m²)
Up to 100 ft² (9.29 m²):
4 motor locations. Damper to be ordered with vertical jackshafts.
Operated from either the top or the bottom with a minimum of 1 motor, direct-coupled to each of the following sections' drive rods: left and right.
NOTE:
Three sections cannot be connected with vertical jackhafts. A maximum of two sections can be connected vertically.
Configurations Using Vertical Jackshafts