Installed In Duct

Control Dampers

MINIMUM SECTION SIZE:
6½”w x 6¾”h (166 mm x 172 mm)

MAXIMUM SECTION SIZE:
25 ft² (2.3 m²)
60″w x 60″h (1524 mm x 1524 mm) or
48″w x 75″h (1220 mm x 1905 mm)

  • Features
  • Documents
  • Applies to SP and NP Profiles only. Not available for WP Profile.
  • Damper is manufactured so that the finished outside frame dimensions are ½” (12.7 mm) smaller than specified opening width & height dimensions.
  • Linkage must remain accessible after installation.
  • In Duct Install Type, single section dampers are constructed with a 2″ (51 mm) flange behind the linkage and a ¾” (19 mm) flange at the front of the linkage, to facilitate access from the face side of the damper.
  • Linkage for multi-section dampers is located where damper sections meet and can be accessed from the face side of the damper assembly.
  • Tamco recommends that Series 9000 BF dampers should not be ordered as In Duct Install Type. Duct work will create a thermal bridge, thereby eliminating the effectiveness and purpose of the thermal break in the damper frame.
  • Always provide opening width and height dimensions, when ordering. Width dimension is always parallel to blades. Height dimension is always perpendicular to blades.

Tamco Aluminum Damper Installation Guidelines

Download PDF Document