Installation Guidelines for aluminum control

Vertical Blade Dampers
single-section and two-section installation

Single-section and two-section vertical blade dampers

SINGLE-SECTION VERTICAL BLADE DAMPERS:

  • TAMCO recommends that single-section vertical blade dampers be installed so that linkage is located at the top.
  • The actuator should be mounted on the drive rod which extends beyond the bottom of the damper.
  • The lower frame of the damper must be properly braced and supported.
    Contact TAMCO Customer Service for configurations not shown.

TWO-SECTION VERTICAL BLADE DAMPERS:

  • Actuators must be mounted on the drive rods.
  • Damper sections may be connected with a jumper. (If sections are connected, the damper must be actuated from only one motor location, either the top or the bottom drive rod.)
  • The lower frame of the damper must be properly braced and supported.
    Contact TAMCO Customer Service for configurations not shown.